Belden 1032A Inst, 1 Pr #18 Str BC, PVC Ins E1, OS, Blk PVC Jkt, 300V PLTC-ER ITC-ER CMG Supplier in Dubai UAE
Enquire on Whatsapp
SKU:
Belden 1032A
Category: Belden
Description
Product Overview
| Suitable Applications | Industrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, …),low voltage digital control (24v, …), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners |
|---|
Construction Details
CONDUCTOR
| Element | Number of Element | AWG | Stranding | Material |
|---|---|---|---|---|
| Pair(s) | 1 | 18 | 7×26 | BC – Bare Copper |
INSULATION
| Element | Material | Thickness | Color Code |
|---|---|---|---|
| Pair(s) | PVC – Polyvinyl Chloride | 0.017 in (0.43 mm) | Black, White |
OUTER SHIELD MATERIAL
| Shield Type | Material | Coverage | Drainwire Type |
|---|---|---|---|
| Tape | Bi-Laminate (Alum+Poly) | 100% | 20 AWG (7×28) TC |
OUTER JACKET MATERIAL
| Material | Thickness | Nom. Diameter | Ripcord |
|---|---|---|---|
| PVC – Polyvinyl Chloride | 0.037 in (0.94 mm) | 0.237 in | Yes |
| Cable Diameter (Nominal) | 0.237 in (6.02 mm) |
|---|
Electrical Characteristics
ELECTRICALS
| Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Max. Current |
|---|---|---|---|---|
| Pair(s) | 5.86 Ohm/1000ft (19.2 Ohm/km) | 51 pF/ft (170 pF/m) | 95 pF/ft (310 pF/m) | 8 Amps per conductor @ 25°C |
| Comm Wire | 14.7 Ohm/1000ft (48.2 Ohm/km) |
| Nom. Outer Shield DCR | 5.07 Ohm/1000ft |
|---|
VOLTAGE
| UL Voltage Rating |
|---|
| 300 V (CMG, PLTC-ER, UL AWM 2464), 150 V (ITC-ER) |
Mechanical Characteristics
TEMPERATURE
| UL Rating | Operating |
|---|---|
| 105°C | -30°C to +105°C |
BEND RADIUS
| Stationary Min. | Installation Min. |
|---|---|
| 2.4 in (61 mm) | 2.4 in (61 mm) |
| Max. Pull Tension | 26 lbs (12 kg) |
|---|---|
| Bulk Cable Weight | 30 lbs/1000ft |
Standards and Compliance
| Environmental Suitability | Indoor/Outdoor, Indoor, Outdoor, Sunlight Resistance |
|---|---|
| Flammability / Fire Resistance | UL1685 (FT4 Loading), FT4, 1202 |
| NEC / UL Compliance | Article 725, Article 727, Article 800, CMG, PLTC-ER, ITC-ER |
| AWM Compliance | 2464 |
| CEC / C(UL) Compliance | CMG |
| European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
History
| Update and Revision | Revision Number: 0.377 Revision Date: 06-08-2021 |
|---|